CONTROLADOR ATC-100
Consultar precio
The ATC-100 is a comprehensive and multifunctional microprocessor-based ATS controller. It is a compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels.The ATC provides both fixed and jumper-selectable settings to allow for a range of applications. It operates from all system voltages between 120 and 480 Vac, single-phase and three phase at 50 or 60 Hz. The ATC-100 monitors the condition of the three-phase line to line voltage and the frequency of both the utility and generator power sources. It can also be set up for single-phase operation. The ATC-100 provides the necessary intelligence to ensure that the transfer switch operates properly through a series of selectable sensing and timing functions.
Características destacadas del producto
- Input Control Voltage
- 95 to 145 Vac 50/60 Hz
- Voltage Measurements of Utility
- V<sub>AB</sub> generator V<sub>AB</sub><br>V<sub>BC</sub> generator V<sub>BC</sub><br>V<sub>CA</sub> generator V<sub>CA</sub>
- Voltage Measurement Range
- 0 to 575 Vac rms (50/60 Hz)
- Voltage Measurement Accuracy
- ± 1% of full scale
- Frequency Measurements Of
- Generador
- Frequency Measurement Range
- 40 Hz to 70 Hz
- Frequency Measurement Accuracy
- ±0.3 Hz over the measurement range
- Undervoltage Dropout
- 80% of the nominal system voltage
- Undervoltage Pickup
- 90% of the nominal system voltage
- Underfrequency Dropout Range
- 90% of the nominal system frequency
- Underfrequency Pickup Range
- 95% of the nominal system frequency
- Overfrequency Dropout Range
- 115% of the nominal system frequency
- Overfrequency Pickup Range
- 110% of the nominal system frequency
- Operating Temperature Range
- –20 to +70°C (–4 to +158°F)
- Storage Temperature Range
- –30 to +85°C (–22 to +185°F)
- Operating Humidity
- 0 to 95% relative humidity (noncondensing)
- Entorno operativo
- Resistant to ammonia, methane, nitrogen, hydrogen and hydrocarbons
- Generator Start Relay
- 5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load
- K1, K2 Relays
- <br>10A, 1–3 hp @ 250 Vac</br><br>10A@30 Vdc</br>
- Pruebas aplicables
- UL-recognized component<br>UL 1008, UL 991 Environmental IEC 61000-4-2, 61000-4-3, 61000-4-4,
- Applicable Testing Continued
- 61000-4-5, 61000-4-6, 61000-4-11<br>CISPR 11, Class B<br>FCC Part 15, Class B<br>CSS 22.2-178
- Enclosure Compatibility
- NEMA 1, NEMA 3R and NEMA 12<br>UV-resistant ATC-100 faceplate